Evaluation of HLW glass dissolution/alteration kinetics by using micro-channel flow-through test method; Initial glass dissolution rate as a function of pH and temperature

Inagaki, Yaohiro*; Sakatani, Keiichi*; Yamamura, Yuki*; Mitsui, Seiichiro; Noshita, Kenji*; Miura, Yoshiyuki*; Kanehira, Norio*; Ochi, Eiji*; Mukunoki, Atsushi*; Chiba, Tamotsu*

Dai-7-Kai Saishori, Risaikuru Bukai Semina Tekisuto, p.136 - 137, 2011/01

Conventional static test methods are not appropriate to evaluate glass dissolution behavior at an arbitrarily-fixed condition due to compositional change of the solution with glass dissolution. In this study, we applied a newly-devised micro-channel flow-through test method to measurement of the initial dissolution rates of Japanese simulated waste glasses, JAEA-P0798 and JNFL-KMOC, at arbitrarily-fixed conditions and we evaluated temperature and pH dependence of glass dissolution. The results showed that the initial dissolution rate increased with temperature and had "V-shaped" pH dependence at each temperature.

Journal Articles

Prevention of false alarms from automatic fire alarm system in the Tokai Reprocessing Plant

Ishii, Takahiro; Shimizu, Kazuyuki; Sakai, Katsumi; Inami, Shinichi

Dai-7-Kai Saishori, Risaikuru Bukai Semina Tekisuto, p.172 - 173, 2011/01

The automatic fire alarm system installed in the Tokai Reprocessing Plant consists of more than 5,000 detectors in about 40 facilities for the moment. In this system, 57 non-fire cases have occurred for about 10 years from January 2001 to December 2010. and about half of these cases was due to the condensation of water vapor generated on the sensor. Therefore, the prevention of condensation is necessary to reduce such false alarms, and the measure for prevention of condensation has been taken by installing a mount for the detector basement. This mount facilitates that the detector does not contact directly to the surface of ceiling where is likely to change an environment due to changeable temperature and humidity. As a result, false alarms caused by condensation have not been found on the detectors with the mounts. This paper reports the details of the improved fire alarm system, and cause/measures for false alarms.

Journal Articles

Optimization of the exchange period on high efficiency particulate air filter in Tokai Reprocessing Plant

Fukuchi, Taira; Sanyoshi, Hirotaka; Yatogi, Hideo; Fukuari, Yoshihiro; Inami, Shinichi

Dai-7-Kai Saishori, Risaikuru Bukai Semina Tekisuto, p.170 - 171, 2011/01

no abstracts in English